Send Message

Integrated Gas Steam Boiler Custom Vertical D Type Arrangement High Output

Negotiable
MOQ
Negotiable
Price
Integrated Gas Steam Boiler Custom Vertical D Type Arrangement High Output
Features Gallery Product Description Request A Quote
Features
Specifications
Product Name: Series SZS65 2.5MPa Custom-made Natural Gas Fired Steam Boiler
Steam Capacity: 65kg
Working Efficiency: 92%--98%
After-sales Service Provided: Engineers Available To Service Machinery Overseas
Output: Steam
Warranty: 2 Years
Style: Horizontal
Weight: Depends
Highlight:

natural gas steam boiler

,

gas powered steam boiler

Basic Infomation
Place of Origin: CHINA
Brand Name: OEM
Certification: CE Certification
Model Number: OEM
Payment & Shipping Terms
Packaging Details: Carton, pallet, wooden case or according to customer's package requirements
Delivery Time: 30 working days
Payment Terms: 30% deposit + 70% T/T before shipping
Supply Ability: 20 sets per month
Product Description

Product Discription

 

Series Double Drum Oil and Gas Fired Steam Boiler

 

series dual fuel gas steam boilers, double boilers, vertical D-type arrangement, fast operation of boilers. 1600 degrees Boiler chimney, diaphragm wall, convection tube and condenser, etc., fuel is burned in the boiler furnace, smoke is discharged into the chimney from the convection tube, scattered into the chimney, scattered in the flue. With the comprehensive electromechanical structure, the utilization rate of heat energy ranks first in the country.

 

 

Product Features

1. Miscellaneous fuels:

The furnace area is large, fuel combustion is sufficient, especially suitable for low -calorific fuels such as coke oven gas, blast furnace gas, etc. The efficiency of burning high -calorific fuels is better, such as natural gas, liquefied gas, etc.

 

2. Capacity overload:

The temperature is high, the baking area is large, the output is strong and has a certain capacity of overload.

 

3. Sensible structure:

The front water wall in front of the boiler is easy to repair the burner head, ensure water level and cooling near the burner, help eliminate carbon deposition in the burner and make fuel combustion more complete.

 

4. Easy to maintain:

On the wall of the boiler, an explosion -resistant door, an anti -fire door and a door for rebuilding are placed, and a pressure opening is set on the front and back sides of the boiler to facilitate the transfer of the boiler.

 

5. Reduce heat loss:

A solid insulation layer is adopted to reduce the heat loss of boilers and improve the thermal efficiency.

 

6.  Long life and longevity:

Excellent professional design, advanced manufacturing technology, strict quality control and control are the guarantee of the quality of each boiler. The normal life of the boiler is more than twenty years.

 

 

Techinical Parameters

Main Parameters of Series Oil & Gas Fired Steam Boiler

Steam Capacity t/h 10 15 20 25 35 50 65
Working Pressure MPa 1.25/1.6 1.25/1.6 1.25/1.6 1.25/1.6 1.25/1.6 1.6/2.5 1.6/2.5
Steam Temperature 193/204 193/204 193/204 193/204 193/204 204/226 204/226
Feed Water Temperature 104 104 104 104 104 104 104
Thermal Efficiency / ≥98%
Fuel / Natural Gas, Liquefied Gas, City Gas, Light Oil
Fuel Consumption Natural Gas NM3/h 733 1098 1464 1829 2559 3662 4769
Liquefied Gas Kg/h 588 883 1173 1469 2053 2937 3823
City Gas NM3/h 1573 2362 3143 3945 5503 7877 10222
Light Oil Kg/h 601 898 1197 1496 2093 2997 3893
Gas Inlet Pressure Natural Gas Mbar 150-200 150-300 150-300 150-300 150-300 150-300 150-300
City Gas Mbar 150-200 150-300 150-300 150-300 150-300 150-300 150-30


Remarks: The fuel consumption in above table are counted the low calorific value of light oil as 42915 KJ/Kg(10260Kcal/Kg), the low calorific value of natural gas as 35588 KJ/NM3(8500Kcal/NM3), the low calorific value of liquefied oil as 45998 KJ/Kg(11000Kcal/Kg), the low calorific value of city gas as 16750 KJ/NM3(4000Kcal/NM3).

 

 

Transport Dimension

 

L mm 5633 6365 6665 Separated Transport Separated Transport Separated Transport Separated Transport
W mm 3300 3585 3585
H mm 3400 3478 3850
Main Steam Valve Pipe Diameter DN mm 150 150 200 200 250 2×150 2×150
Feed Water Valve DN mm 50 65 65 80 100 125 125
Drain Valve Pipe Diameter DN mm 40 40 50 50 50 50 50
Chimney Diameter DN mm 750 1000 1100 1300 1500 2000 2000

External and Interface Dimension of Series Oil & Gas Fired Steam Boiler

Remarks: We will reserve rights to change the above mentioned data due to continuous policy transformation and product improvement.

 

 

 

 

Recommended Products
Get in touch with us
Contact Person : furnacess
Tel : + 86 17733330123
Fax : 86-10-34242423-33
Characters Remaining(20/3000)